
VS-616G5 Programming Manual 97
Setting Range: 0.0 to 1000.0%
Factory Default: 100.0%
Sets the terminal 16 input gain level when the reference voltage is 10V. See Figure 46, on page 95.
Setting Range: -100.0 to 100.0%
Factory Default: 0.0%
Sets the terminal 16 input bias level when the reference voltage is 0V. See Figure 46, on page 95.
H3-06 Terminal 16 Reference % Gain Terminal 16 Gain
B B B B
H3-07 Terminal 16 Reference ±% Bias Terminal 16 Bias
B B B B
· Torque Compensation (setting: “14”)
100%
-10V
10V
-100%
0
100%
-10V
10V
0
100%
-10V 10V0
10%
1V
100%
-10V 10V0
100%
-10V 10V0
30%
3V
100%
10V
-100%
0
· Auxiliary Frequency Reference (setting: “0”)
· Frequency Gain (setting: “1”)
· Frequency Bias (setting: “2”)
· Voltage Bias (setting: “4”)
· Accel/Decel Change (setting: “5”)
· DC Injection Braking Current (setting: “6”)
· Overtorque Level (setting: “7”)
· Stall Prevention Level (setting: “8”)
· Reference Lower Limit (setting: “9”)
· Jump Frequency (setting: “A”)
· PID Feedback (setting: “B”)
· Forward Torque Limit (setting: “10”)
· Reverse Torque Limit (setting: “11”)
· Regenerative Torque Limit (setting: “12”)
· Torque Reference (setting: “13”)
· Forward/Reverse
Figure 47 Multi-function Analog Input Selection
Torque Limit
(setting: “15”)
Section H: Control Circuit Terminals
H3 Analog Inputs
Comentarios a estos manuales