74 VS-616G5 Programming Manual
Section F: Option Parameters
F9 CP-916 Option Set-up
F9 CP-916 Setup
The CP-916 option card provides PLC and motion type functions. This allows the G5 inverter to be a
stand alone control system.
The CP-916 option card connects to the control board at 3CN.
When the CP-916 option is installed, the 4CN speed feedback option port is the only option port that is
supported.
Specifications
• RS 232C communication port - Used for programming the CP-916G and for communication to
other devices such as PLC’s or printers.
• High speed (4 Mb/s) peer to peer communication port.
• Available protocol;
MEMOBUS (MODBUS) 19.2 kbps maximum.
Application Download Tool 19.2 kbps maximum.
CP 717 Programming Tool 9.6 kbps.
Parameter F9-01 selects the initial state for an external fault condition when the inverter is configured
for serial communication using the CP-916.
The “EFO” fault code will be displayed.
Parameter F9-02 selects the condition of detection for an external fault when using the CP-916 option.
F9-01 Option External Fault Selection EFO Selection
A A A A
Setting Description
0 When closed, the inverter will trip. (factory default)
1 When open, the inverter will trip.
F9-02 Option External Fault Detection EFO Detection
A A A A
Setting Description
0 The fault will always be detected, even when the drive is
stopped. (factory default)
1 The fault will be detected only when the drive is running.