Yaskawa VS-616G5 Series Revision F Programming Manual Manual de usuario Pagina 73

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 162
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 72
VS-616G5 Programming Manual 73
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
F7 PO-36F Set-up
The PO-36F option card outputs pulse signals that correspond to the inverter output frequency. These
signals are used in master/slave configurations where speed matching is needed.
.
Sets the number of pulse signals to be output from the PO-36F option.
F8 Function F8 SI-F/G Set-up
The setting of parameter F8-01 selects the stopping method when an E-15 fault is detected.
An E-15 fault may occur when using the SI-F or SI-G communication options. The fault will occur
after initial communication has been established then the connection is lost. The following fault code
will be displayed:
F7-01 PO-36F Pulse Monitor Output Selection PO-36F Selection
A A A A
Setting Number of Output Pulses
0 Inverter output frequency × 1
1 Inverter output frequency × 6 (factory default)
2 Inverter output frequency × 10
3 Inverter output frequency × 12
4 Inverter output frequency × 36
F8-01 (E-15) Detection Stopping Method E-15 Det Sel
A A A A
Setting Description
0 Ramp to stop according to C1-02 set value
1 Coast to stop.
2 Ramp to stop according to C1-09 set value.
3 Alarm flashes, operation continues.
Section F: Option Parameters
F7 PO-36F & F8 SI-F/G Option Set-up
Vista de pagina 72
1 2 ... 68 69 70 71 72 73 74 75 76 77 78 ... 161 162

Comentarios a estos manuales

Sin comentarios