VS-616G5 Programming Manual 79
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
It is possible to mix analog and digital references in the multi-speed input function. The parameters
must be set as shown below
.
· Multi Accel/Dec1 (Set value = 7)
Open: Acceleration 1 / Deceleration 1 is set by parameters C1-01and C1-02 respectively.
Closed: Acceleration 2 / Deceleration 2 is set by parameters C1-03 and C1-04 respectively.
· External Baseblock N.O. (setting: “8”)
Baseblock operation is performed when the contact output is closed. External baseblock operation
differs as described below, depending on the run command input status.
When an external baseblock signal is input while the inverter is running, BB blinks on the digital
operator display, and the inverter output is shut OFF. When the external baseblock signal is
removed, operation restarts at the previous frequency reference before baseblock. Output voltage is
then increased up to its previous level before baseblock, in the voltage recovery time (L2-04).
When a stop signal is input and an external baseblock signal is input while the inverter is decelerat-
ing, BB blinks on the digital operator, the inverter output shuts OFF and the frequency reference is
set to 0.
Parameter Reference Digital Analog
(d1-01) Reference 1 b1-01 = 0 b1-01 = 1 (terminal 13 or 14)
(d1-02) Reference 2 H3-05
0 H3-05 = 0 (terminal 16)
(d1-03) Reference 3 d1-03
(d1-04) Reference 4 d1-04
(d1-05) Reference 5 d1-05
(d1-06) Reference 6 d1-06 not available
(d1-07) Reference 7 d1-07
(d1-08) Reference 8 d1-08
(d1-09) Jog Reference d1-09
Accel Time 1
(C1-01)
Decel Time 1
(C1-02)
Accel Time 2
(C1-03)
Decel Time 2
(C1-04)
Decel Time 1
(C1-02)
Output
Frequency
FWD (REV)
Run Command
Accel/Decel
Time Selection
(Terminals 3 to 8)
t
t
t
Section H: Control Circuit Terminals