Yaskawa VS-616G5 Series Revision F Programming Manual Manual de usuario Pagina 84

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 162
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 83
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
84 VS-616G5 Programming Manual
Section H: Control Circuit Terminals
H1 Digital Inputs
· Terminal 13/14 Selection (setting: “1F”)
Open: Terminal 13 is used for the master frequency reference.
Closed: Terminal 14 is used for the master frequency reference.
Note: When the set value of Terminal 14 Selection (H3-09) is other than “1F” and the contact input
is set for terminal 13/14 selection (H1-__ = “1F”), a setting error (OPE3) occurs.
· External Fault (setting: “20-2F”)
Use this contact input to select how the inverter responds to an external fault.
Notes:
1. N.O. = normally open contact; N.C. = normally closed contact
2. Setting “24” is the factory default.
3. Set up the external fault function according to the following tree:
External Fault Selection
Setting
Result
Input Level Selection Detection Method External Fault Action
N.O. N.C. Always During Run Ramp to Stop Coast to Stop Fast-stop Alarm Only
20
24
28
2C
22
26
2A
2E
21
25
29
2D
23
27
2B
2F
Vista de pagina 83
1 2 ... 79 80 81 82 83 84 85 86 87 88 89 ... 161 162

Comentarios a estos manuales

Sin comentarios