84 VS-616G5 Programming Manual
Section H: Control Circuit Terminals
H1 Digital Inputs
· Terminal 13/14 Selection (setting: “1F”)
Open: Terminal 13 is used for the master frequency reference.
Closed: Terminal 14 is used for the master frequency reference.
Note: When the set value of Terminal 14 Selection (H3-09) is other than “1F” and the contact input
is set for terminal 13/14 selection (H1-__ = “1F”), a setting error (OPE3) occurs.
· External Fault (setting: “20-2F”)
Use this contact input to select how the inverter responds to an external fault.
Notes:
1. N.O. = normally open contact; N.C. = normally closed contact
2. Setting “24” is the factory default.
3. Set up the external fault function according to the following tree:
External Fault Selection
Setting
Result
Input Level Selection Detection Method External Fault Action
N.O. N.C. Always During Run Ramp to Stop Coast to Stop Fast-stop Alarm Only
√ √ √ 20
√ √ √ 24
√ √ √ 28
√ √ √ 2C
√ √ √ 22
√ √ √ 26
√ √ √ 2A
√ √ √ 2E
√ √ √ 21
√ √ √ 25
√ √ √ 29
√ √ √ 2D
√ √ √ 23
√ √ √ 27
√ √ √ 2B
√ √ √ 2F