VS-616G5 Programming Manual 85
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
· PID Integral reset (Set value = 30)
Open: PID Integral values are added.
Closed: PID Integral value is set to zero.
· PID Control Integral Hold (Set value = 31) <1110>
Closed: Integral value of the PID control is held.
· DC Injection Braking Command (setting: “60”)
When a DC injection braking command is input while the inverter is stopped, DC injection braking
operation is activated. When a run command or a jog command is input, DC injection braking is
released to start operation (operation has priority).
H1-__ = “24”
Depress the Data/Enter key.
Input Level Selection
Detection Method
External Fault Action
N.O. Contact
N.C. Contact
Always
During Run
Ramp to Stop
Coast to Stop
Fast-stop
Depress
Alarm Only
the key.
DC Injection Braking Command
Fwd Run Command
ON
OFF
OFF
Output Frequency
ON
OFF
OFF
DC Injection
Braking
DC Injection
Braking
DC Injection Braking
Start Frequency
(B2-01)
Figure 35 DC Injection Braking Contact Input Timing Diagram
Section H: Control Circuit Terminals