
VS-616G5 Programming Manual 41
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
Setting Range: 0 to 400%
Factory Default: 400%
.Parameter C5-08 adjusts the amount of Integral control of the automatic speed regulator in the Closed
Loop Flux Vector control mode. Setting parameter C5-08 to zero will make the ASR control propor-
tional. Setting C5-08 to 400% will make the ASR control proportional and integral.
C6 Carrier Frequency
This function sets the inverter output transistor switching frequency (carrier frequency). Increase the
carrier frequency to reduce motor noise and decrease it to reduce leakage current.
Setting Range: 0.4 to 15.0kHz
Factory Default: 15.0Hz*
For constant carrier frequency operation, set the gain (C6-03) to “0”, and set the upper limit (C6-01)
and lower limit (C6-02) to the same value.
* Factory defaults vary depending on drive rating. See the following table for more details:
C5-08 ASR Integral Limit ASR I Limit
- - - A
C6-01 Carrier Frequency Upper Limit CarrierFreq Max
B B B B
C6-02 Carrier Frequency Lower Limit CarrierFreq Min
A A - -
Speed
Slip
Torque
C5-08=0
P Control
C5-08=400%
P-I Control
Section C: Tuning Parameters
C6 Carrier Frequency
Comentarios a estos manuales