VS-616G5 Programming Manual 89
· During Run (setting: “0”)
Closes when a run command is input, or when the inverter outputs voltage.
· Zero-speed (setting: “1”)
Closes when the inverter output frequency is less than the minimum output frequency (El-09) during
V/f control with PG feedback. Closes when the motor speed is less than the zero-speed level (B2-01)
during flux vector control.
5 Frequency detection 2
6 Inverter ready
7 DC bus undervoltage
8 Baseblock 1
9 Option reference
A Remote operation
B Torque detection 1 (N.O.)
C Loss of reference
D DB overheat
E Fault
F Not used
10 Minor fault
11 Reset command active
12 Timer output
13 Frequency agree 2
14 Desired frequency agree 2
15 Frequency detection 3
16 Frequency detection 4
17 Torque detection 1 (N.C.)
18 Torque detection 2 (N.O.)
19 Torque detection 2 (N.C.)
1A Reverse direction
1B Baseblock 2
1C Motor 2 Selection
1D Regenerating
1E Restart enabled
1F Overload (OL1)
20 OH pre-alarm
30 Current/torque limit
31 Speed limit
33 Zero servo completion
37 During run 2
H2-01
to 3
Setting
Function
Control Method (A1-02)
Reference
Page
V/f V/f w/ PG
Open Loop
Vector
Flux Vector
Section H: Control Circuit Terminals
H2 Digital Outputs