VS-616G5 Programming Manual 11
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
A2 User’s Parameters
The user can select up to 32 parameters for quick-access programming. By setting the user access level
(A1-01) to “User Program”, only the parameters selected in function A2 can be accessed by the user.
Parameter A1-01 must be set to 4 (advanced access level) to input parameter numbers into A2-01
through A2-32, and then A1-01 must be set to 1 (User Level) for only the user selected parameters to
be viewed.
Main Menu: Programming <ENTER>
B Application Parameters
B1 Sequence
Frequency reference and run command can be set independently as shown below:
* Setting parameter B1-01 or B1-02 to 4 allows reference and/or run source from CP-717 when
either CP-916 or CP-216 option cards are installed.
By depressing the LOCAL/REMOTE key on the digital operator, the operation mode can be
selected as shown below:
Local: Operation according to frequency reference and run command from digital operator.
Remote: Operation according to frequency reference and run command set by B1-01 and B1-
02.
The digital operator is reset to remote operation when power is cycled.
B1-01 Frequency Reference Selection Reference Source
Q Q Q Q
B1-02 Operation Method Selection Run Source
Q Q Q Q
Setting Description
0 Command from digital operator
1 Command from control circuit terminal (factory default)
2 Command from serial communication
3 Command from option card
4 EWS (Reference from CP-717)* <1110>
This setting will be used with the CP-717 to run and change
the reference through DP-RAM.
Section B: Application Parameters
A2 User Parameters and B1 Sequence