122 VS-616G5 Programming Manual
Section L: Operator Parameters
O2 Key Selections
Sets the display units for parameters and monitors related to frequency, in the flux vector control mode.
Selects how the parameter addresses are displayed on the digital operator.
O2 Key Selections
Enables/disables the digital operator LOCAL/REMOTE key.
Enables/disables the digital operator STOP key, during operation from the external terminals and dur-
ing serial communication.
O1-04 Display Units for Speed-Related Parameters Display Units
B
Setting Description
0 Displays frequency in Hz (factory default).
1 Displays frequency in rpm.
O1-05 Parameter Selection Address Display
A A A A
Setting Description
0 Displays parameter number (factory default).
1 Displays MODBUS address.
O2-01 Local/Remote Key Local/Remote Key
B B B B
Setting Description
0 Local/Remote key is disabled.
1 Local/Remote key is enabled (factory default).
Depressing the Local/Remote key switches operation commands
between the digital operator and the settings of B1-01 and B1-02.
O2-02 STOP Key During External Terminal Operation Oper STOP Key
B B B B
Setting Description
0 The digital operator STOP key is disabled when Run command does not come from the dig-
ital operator.
1 The digital operator STOP key is always enabled (factory default).
The STOP key is enabled even during external terminal operation and serial communication.