VS-616G5 Programming Manual 101
H5 Serial Communication Set-up
The inverter uses communication port 6CN to communicate via MODBUS protocol.
Setting Range: 0 to 1F
Factory Default: 1F
Selects a station address for identification of the inverter during serial communication.
Selects the baud rate at which the inverter serially communicates with external devices.
Selects the transmission parity for the 6CN MODBUS port.
H5-01 Serial Communication Station Address Serial Comm Adr
A A A A
H5-02 Serial Communication Baud Rate Serial Baud Rate
A A A A
Setting Description
0 1200 Baud per Second
1 2400 Baud per Second
2 4800 Baud per Second
3 9600 Baud per Second (factory default)
4 19200 Baud <1110>
H5-03 Serial Communication Parity Selection Serial Com Sel
A A A A
Setting Description
0 No parity (factory default)
1 Even parity
2 Odd parity
Section H: Control Circuit Terminals
H5 Serial Communication Set-up