VS-616G5 Programming Manual 63
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
Sets the motor phase-to-phase resistance value in units of 0.01W.
The default setting varies depending on the inverter model setting (O2-04).
Sets the motor leakage inductance in units of 0.1%. The default setting varies depending on the
inverter model setting (O2-04).
F Option Parameters
F1 PG Option Set-up
These parameters can be accessed during operation using a pulse generator (PG) for speed feedback.
When access level is BASIC (A1-03), the parameter is not displayed unless the option card is con-
nected.
Setting Range: 0 to 60000
Factory Default: 1024
Sets the number of PG pulses per motor revolution (pulses/rev).
Selects the stopping method when a disconnected PG is detected.
E5-05 Motor 2 Terminal Resistance Term Resistance
A A A A
E5-06 Motor 2 Leakage Inductance Leak Inductance
A
−
A A
F1-01 PG Pulses per Revolution PG Pulses/Rev
−
Q
−
Q
F1-02 PG Disconnection Detection Stopping Method PG Fdbk Loss Sel
−
B
−
B
Setting Description
0 Ramp to stop - according to C1-02
1 Coast to stop (factory default)
2 Fast-stop according to C1-09
3 Alarm flashes, operation continues (this setting is disabled
during flux vector control)
Phase-to-Phase Resistance at
273 + (25ºC + insulation class temperature) / 2
273 + insulation class temperature
Motor Terminal Resistance =
Insulation Class Temperature
×
Section F: Option Parameters
F1 PG Option Set-up