108 VS-616G5 Programming Manual
Section L: Protection Parameters
L3 Stall Prevention / Current Limit
Setting Range: 0 to 200%
Factory Default: 150%
The stall prevention/current limit level during acceleration is set as a percentage of inverter rated cur-
rent. A setting of 200% disables current limit during acceleration. During acceleration, if the output
current exceeds this current limit level (L3-02), acceleration stops and frequency is maintained. When
the output current decreases below this current limit level (L3-02), acceleration restarts.
When a motor is used in the constant output area (constant HP), output frequency max. voltage out-
put frequency (E1-06). In this area, the stall prevention/current limit level during acceleration is auto-
matically reduced for smoother acceleration. This parameter limits the stall prevention/current limit
level during acceleration in the constant output area so that it does not decrease unnecessarily. The
current limit level during acceleration is changed according to the following equation:
L3-02 Stall Prevention Level During Acceleration StallP Accel Lvl
B B B
L3-03 Stall Prevention Limit (constant output area) StallP CHP Level
A A A
Motor Current
L3-02
Time
Output Frequency
Time
*
* Controls the acceleration rate to
prevent the inverter from tripping.
Figure 52 Stall Prevention/Current Limit During Acceleration
Current Limit Level During
Accel in Constant Output Area
Current Limit Level During
Acceleration (L3-02)
Max. Voltage Output Frequency (E1-06)
Output Frequency
×
=