26 VS-616G5 Programming Manual
Setting Range: 0 to 100%
Factory Default: 1%
This parameter sets the level at which a loss of PID feedback is detected. The PID feedback must be at
or below this level for the time defined by B5-14 before a loss of feedback can be detected. A setting
of 100% represents 100% of the feedback signal.
Setting Range: 0.0 to 25.0
Factory Default: 1.0
This parameter sets the gain of the PID output. The PID output can be monitored by parameter U1-37
PID Output Monitor. Refer to PID Block Diagram Figure 9.
B6 Reference Hold
The reference hold or dwell function is used to temporarily hold the output frequency at a set refer-
ence, for a set time, and then start it again. This function can be used when driving a permanent magnet
motor, or a motor with a heavy starting load. This pause in acceleration allows the magnets in a perma-
nent magnet motor to synchronize with the stator field of the motor, thus reducing traditionally high
starting current.
Setting Range: 0.0 to 400.0Hz
Factory Default: 0.0Hz
Sets the dwell frequency reference during acceleration in units of 0.1Hz.
Setting Range: 0.0 to 10.0s
Factory Default: 0.0s
Sets the amount of time that the frequency reference “dwells” during acceleration in units of 0.1s.
Setting Range: 0.0 to 400.0Hz
Factory Default: 0.0Hz
Sets the dwell frequency reference during deceleration in units of 0.1Hz.
B5-13 PID Feedback Loss Detection Level <1110> Fb los Det Lvl
A A A A
B5-14 PID Output Gain <1110> Output Gain
A A A A
B6-01 Dwell Frequency Reference at Start Dwell Ref @Start
A A A A
B6-02 Dwell Time at Start Dwell Time@Start
A A A A
B6-03 Dwell Frequency Reference at Stop Dwell Ref @Stop
A A A A
Section B: Application Parameters
B6 Reference Hold