VS-616G5 Programming Manual 71
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
F5 DO-02 Set-up
The DO-02C option card has 2 form C type dry contacts. Each of the dry contacts can be individually
set by F5-01 and F5-02.
The DO-02C option card connects to the control board at 3CN.
The table is a list of items that can be selected.
Selects the multi-function output selections for channel 1 of the DO-02C option.
For detailed information on these settings, refer to section H2, Digital Outputs, on page 88.
Setting Range: Same as F5-01
Factory Default: Zero speed (setting = “1”)
Selects the multi-function output selections for channel 2 of the DO-02C option.
F5-01 DO-02C Digital Output Channel 1 Selection DO-02 CH1 Select
A A A A
Setting Description Setting Description
0 During run 1 (factory default) 13 Fref/Fout agree 2
1 Zero speed 14 Fref/set agree 2
2 Fref/Fout agree 1 15 Frequency detection 3
3 Fref/set agree 1 16 Frequency detection 4
4 Frequency detection 1 17 Torque detection 1 (N.C.)
5 Frequency detection 2 18 Torque detection 2 (N.O.)
6 Inverter ready 19 Torque detection 2 (N.C.)
7 DC bus undervoltage 1A Reverse direction
8 Baseblock 1 1B Baseblock 2
9 Option frequency reference 1C Motor 2 selected
A Remote operation 1D Regenerating
B Torque detection 1 (N.O.) 1E Restart enabled
C Loss of reference 1F Overload (OL1)
D DB overheat 20 OH pre-alarm
E Fault 30 Current/torque limit
F Not used 31 Speed limit
10 Minor fault 33 Zero servo end
11 Reset command active 37 During run 2
12 Timer output - --
F5-02 DO-02C Digital Output Channel 2 Selection DO-02 CH2 Select
A A A A
Section F: Option Parameters
F5 DO-02 Option Set-up