96 VS-616G5 Programming Manual
Section H: Control Circuit Terminals
H3 Analog Inputs
Selects the type of voltage signal input at terminal 16.
The resolution of terminal 16 is 11 bit.
The following table lists the function selections for the multi-function analog inputs (terminals 14 and
16), and indicates the control modes during which each function can be enabled.
H3-04 Terminal 16 Signal Selection Terminal 16 Sel
B B B B
Setting Description
0 0 to 10V input (factory default)
1 -10 to +10V input
H3-05 Terminal 16 Multi-function Selection Terminal 16 Sel
B B B B
Setting Function
Control Method (A1-02)
Setting Level
V/f V/f w/ PG
Open Loop
Vector
Flux
Vector
0 Aux. Frequency Ref. (factory default) √ √ √ √ ±100% / ±10V
1 Frequency Gain √ √ √ √ 100% / 10V
2 Frequency Bias √ √ √ √ ±100% / ±10V
4 Voltage Bias √ √ − − 100% / 10V
5 Accel/Decel Change √ √ √ √ 100% / 1V
6 DC Injection Braking Current √ √ √ − 100% / 10V
7 Overtorque Level √ √ √ √ 100% / 10V
8 Stall Prevention Level √ √ − − 100% / 10V
9 Reference Lower Limit √ √ √ √ 100% / 10V
A Jump Frequency √ √ √ √ 100% / 10V
B PID Feedback √ √ √ √ ±100% / ±10V
C PID Reference Bias <1110> √ √ √ √ 10V/Fmax
D Frequency Reference Bias 2 <1110> √ √ √ √ 10V/Fmax
10 Forward Torque Limit − − √ √ 100% / ±10V
11 Reverse Torque Limit − − √ √ 100% / ±10V
12 Regenerative Torque Limit − − √ √ 100% / ±10V
13 Torque Reference − − − √ ±100% / ±10V
14 Torque Compensation − − − √ ±100% / ±10V
15 Forward/Reverse Torque Limit − − √ √ ±100% / 10V
1F Not Used − − − − −