Yaskawa MP2000 Series I/O Module User Manual Manual de usuario Pagina 95

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 139
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 94
4.2 Specifications of LIO-06 Module Connections
4.2.5 Analog Input Circuit
95
4
LIO-06 Module
4.2.5 Analog Input Circuit
The following table shows the LIO-06 Module analog input circuit specifications.
* Input conversion time = Delay time from input filter (1 ms max.) + 50 μs;
Delay time from the input filter peaks at 1 ms between -10 and +10 V.
4.2.6 Analog Output Circuit
The following table shows the LIO-06 Module analog output circuit specifications.
Item Specifications
Number of Channels
1 channel
Isolation Method
Non-isolated
Analog Input Range
-10 to +10 V
Max. Rated Input
±15 V
Input Impedance
Approx. 20 kΩ
Resolution
16 bits (-31276 to +31276)
Accuracy
25°C
±0.1% (±10 mV)
0 to 50°C
±0.3% (±30 mV)
Input Conversion Time *
1.05 ms max.
Item Specifications
Number of Channels
1 channel
Isolation Method
Non-isolated
Analog Output Range
-10 to +10 V
Output Impedance
20 kΩ max.
Resolution
16 bits (-31276 to +31276)
Accuracy
25°C
±0.1% (±10 mV)
0 to 50°C
±0.3% (±30 mV)
Max. Allowable Load Current
±5 mA
Output Delay Time
1.2 ms (after change with a full scale of -10 to +10 V)
Vista de pagina 94
1 2 ... 90 91 92 93 94 95 96 97 98 99 100 ... 138 139

Comentarios a estos manuales

Sin comentarios