5.2 Specifications of DO-01 Module Connections
5.2.4 DO-01 Module Connections
131
5
DO-01 Module
If you connect an inductive load, connect a diode parallel to the load to
absorb counter electromotive force.
Backward voltage: 10 times the load voltage or greater
Forward current: Load current or greater
OUT
diode
Source circuit
+
COM
Inductive
load