3.1 Outline of LIO-04/LIO-05 Modules
3.1.4 LED Indicators
66
( 3 ) Number of Simultaneously ON Inputs - Ambient Temperature Characteristics
The following graph shows the number of inputs that can be simultaneously ON depending on the ambient tempera-
ture.
3.1.4 LED Indicators
The following table shows the LIO-04/LIO-05 Module status when each indicator lamp is lit or unlit.
0
0
10
5
15
20
25
30
35
(Number of inputs)
10 20 30
Ambient Temperature
40 50 60 㧔͠㧕
(10 inputs at 55͠㧕
(16 inputs at 55͠㧕
(32 inputs at 41͠㧕
(Input voltage: 24 VDC)
(Input voltage: 28.8 VDC)
(32 inputs at 28͠㧕
Number of
Simultaneously
ON Inputs
Indicator Color When Lit When Unlit
RUN Green
Normal operation Error occurrence
FUSE Red
One or some of the output protection
fuses is blown out.
Output protection fuses are normal.