98 VS-616PS5 Programming Manual
460 V Models
Selects whether the ENTER key is used when the frequency reference is set by the
digital operator. The digital operator can simulate a motor operated potentiometer
(M.O.P.) by setting this parameter.
If the digital operator is disconnected from the inverter, this parameter selects
whether the inverter detects this condition.
This function can only be activated when the run command comes from the digital
operator.
Setting Range: 0 to 65535 Hours
Factory Default: 0 Hours
Sets the initial value for the cumulative operation time. Operation time starts accu-
mulating from the set value. Commonly used for preventive maintenance purposes.
Model 40P4 40P7 41P5 42P2 43P7 44P0 45P5 47P5 4011 4015 4018 4022 4030 4037 4045
02-04 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E
C6-02
(KHz)
8 8 8 8 8 8 8 8 8 8 8 8 8 4 4
L2-02
(sec)
1.0 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Model 4055 4075 4110 4160 4185 4220 4300
02-04 2F 30 32 34 35 36 37
C6-02
(KHz)
4 4 4 4 2 2 2
L2-02 (sec) 2.0 2.0 2.0 2.0 2.0 2.0 2.0
O2-05 Digital Operator M.O.P. Mode Selection A
Setting Description
0 The digital operator M.O.P. mode is disabled (factory default). The inverter accepts the refer-
ence command when the ENTER key is depressed.
1 The digital operator M.O.P. mode is enabled. The inverter accepts the reference command as
soon as changes are made with the arrow keys, without the ENTER key being depressed.
O2-06 Digital Operator Disconnection Detection A
Setting Description
0 Detection is disabled. Operation continues (factory default).
1 Detection is enabled. When the inverter detects that the digital operator has been disconnected while
running, the inverter coasts to stop and the error message “OPR ” is displayed on the digital operator,
after it has been connected again.
O2-07 Operator Time Setting A
Section O: Parameters
O2 Key Selection