10 VS-616PS5 Programming Manual
Main Menu: Programming <ENTER>
B Application Parameters
B1 Sequence
Setting Range: 0 to 4
Factory Default: 1
Frequency reference and run command can be set independently as shown below:
By depressing the LOCAL/REMOTE key on the digital operator, the operation mode
can be selected as shown below:
Local: Frequency reference and run command from digital operator. (Remote
SEQ and REF LEDs off)
Remote:Operation according to frequency reference and run command set by B1-
01 & B1-02, respectively.
The Control Method is reset to remote operation when power is cycled.
Setting Range: 0 to 3
Factory Default: 0
This function selects the stopping method suitable for the application.
B1-01 Frequency Reference Selection Q
B1-02 Operation Method Selection Q
Setting Description
0 Run by digital operator reference
1 Run by external terminal reference (factory default).
2 Run by serial communication
3 Option card (run by CP-916 B/G, 216 I/F references
4 Run by personal computer (CP-717) reference
6 Pulse Train reference (valid for B1-01 only, used with PG-P2)
B1-03 Stopping Method Selection Q
Setting Description
0 Ramp to stop (factory default).
1 Coast to stop.
3 Coast to stop with timer.
Section B: Application Parameters
B1 Initialization Sequence