
22 VS-616PS5 Programming Manual
B6 Reference Hold
The reference hold or dwell function is used to temporarily hold the output frequency
at a set reference, for a set time, during the acceleration and deceleration process.
Use this function when driving a permanent magnet motor, or a motor with a heavy
starting load. The pause in acceleration allows the magnets in a permanent magnet
motor to synchronize with the stator field of the motor, thus reducing traditionally high
starting current.
Setting Range: 0.00 to 100.00%
Factory Default: 0.00%
Sets the dwell frequency reference during acceleration in units of 0.01%.
Setting Range: 0.0 to 10.0s
Factory Default: 0.0s
Sets the amount of time that the frequency reference “dwells” during acceleration in
units of 0.1s.
Setting Range: 0.00 to 100.00%
Factory Default: 0.00%
Sets the dwell frequency reference during deceleration in units of 0.01%.
Setting Range: 0.0 to 10.0s
Factory Default: 0.0s
Sets the amount of time that the frequency reference “dwells” during deceleration in
units of 0.1s.
B6-01 Dwell Reference at Start A
B6-02 Dwell Time at Start A
B6-03 Dwell Reference at Stop A
B6-04 Dwell Time at Stop A
Section B: Application Parameters
B6 Reference Hold
Comentarios a estos manuales