72 VS-616PS5 Programming Manual
Overtorque Detection 1 - N.C. (setting: “17”)
Opens during overtorque detection 1 (L6-01, see section L6, Overtorque Detec-
tion, on page 81).
Overtorque Detection 2 - N.O. (setting: “18”)
Closes during overtorque detection 2 (L6-01, see section L6, Overtorque Detec-
tion, on page 81).
Overtorque Detection 2 - N.C. (setting: “19”)
Opens during overtorque detection 2 (L6-01, see section L6, Overtorque Detec-
tion, on page 81).
During Reverse Run (setting: “1A”)
Closes during a reverse run command.
Baseblock 2 - N.C. (setting: “1B”)
Opens when the inverter output shuts OFF.
Monitoring/Regenerating Mode (setting: “1D”)
Closes during regenerative operation.
Automatic Restart (setting: “1E”)
Closes during automatic restart operation.
OL1 Pre-alarm (setting: “1F”)
Closes when the motor-calculated electronic thermal overload value increases to
90% of the internal fault detection level.
OH Pre-alarm (setting: “20”)
Closes when the heatsink temperature exceeds the Overheat Temperature Level
(L8-02), or when a multi-function contact input (H1-XX = “B”) closes.
Detection Width 1 (L4-04)
Output Speed
Frequency
ON
Detection Level 1 (L4-03)
Figure 45 Speed Detection 2 Signal Timing Diagram
Detection 4 Signal
OFF OFF
Section H: Control Circuit Terminal Parameters
H2 Digital Outputs