Yaskawa VS-616PS5 Series Programming Manual Manual de usuario Pagina 51

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 113
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 50
VS-616PS5 Programming Manual 51
Setting Range: 0 to 50%
Factory Default: 10%
This sets the excessive speed deviation detection level as a percentage of maximum
output speed (E1-06). Used in conjunction with parameter F1-11 to sense a speed
deviation condition.
Setting Range: 0.0 to 10.0s
Factory Default: 0.5s
This parameter sets the elapsed time for which a speed deviation condition must
exist, before a fault (or alarm) is generated.
A fault (or alarm) signal is output after the deviation between speed reference and the
actual motor speed exceeds the set value of F1-10 and after the time set to F1-11
elapses. The stopping method is set with F1-04. Also, detection is not activated
while accelerating/decelerating or during torque control.
Setting Range: 0.0 to 10.0s
Factory Default: 3.0s
This sets the time for which a PG open condition must exist, before a fault (or alarm)
is generated.
The stopping method, when a “PGO” condition is detected, is selected by param-
eter F1-02.
F1-10 PG Deviation Detection Level A
F1-11 PG Deviation Detection Time A
F1-13 PG Open Detection Delay Time A
Figure 30 Overspeed Detection Timing Diagram
Speed Reference
OFF ON
Motor Speed
F1-10
Speed Deviation
Fault Signal
F1-11
OFF
Section F: Option Parameters
F1 PG Option Set-up
Vista de pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 112 113

Comentarios a estos manuales