VS-616PS5 Programming Manual 9
Main Menu:Initialize <ENTER>
A Initialization Parameters
A1 Initialization Set-up
This parameter allows the “masking” of parameters according to user level. See the
following table:
Use this parameter to reset the inverter to its factory default settings. Initialize the
inverter after changing the control PCB, or after selecting inverter capacity (O2-04).
This parameter allows password entry to view masked parameters.
A1-01 Parameter Access Level Q
Setting Description
0 Operation Only
2 Quick Start Level (factory default) - For maintenance-level programming.
3 Basic Level - For basic programming in most applications.
4 Advanced Level - For advanced programming in special applications.
A1-03 Operator Status Q
Setting Description
0 No Initialization (factory default).
2220 2-Wire Initialization - terminal 1 becomes FWD run command and
terminal 2 becomes REV run command. All other parameters are
reset to their original factory default settings.
3330 3-Wire Initialization - terminal 1 becomes run command, terminal 2
becomes stop command and terminal 3 becomes FWD/REV run
selection. All other parameters are reset to their original factory
default settings.
A1-04 Password Entry Q
Section A: Initialization Parameters
A1 Initialization Set-up