E Motor Parameters
E1 Motor Constant
Setting Range: 180 to 230V (360 to 460V)
Factory Default: 230V (460V)
Set E1-01 to the nominal expected line voltage (exact setting is not required)
This setting adjusts the overvoltage level, the braking transistor turn on level, and the
stall prevention level during deceleration.
Only built-in type braking transistors will be affected, not CDBR units.
Setting Range: 1000 to 1239
Factory Default: 0
Used in conjunction with the motor connection selection (E1-17) to automatically load
the motor parameter (E1-03 thru E1-13) from a pre-programmed look-up table. When
setting E1-02 to any setting other than 1000, be sure to set E1-17 to the proper con-
nection setting first. Then, set E1-03 to the proper motor winding type. When set to
1000, manual entry of parameter E1-03 - E1-13 is required.
Do not change the value after it has been set as the motor parameters will be modi-
fied.
Setting Range: 0.0 to 255.0V (0-510.0 V)
Factory Default: 230.0 (460.0)
Sets the motor rated voltage. Set to 230.0 for 320VDC nameplated motors and 460.0
for 640VDC nameplated motors.
E1-01 Inverter Input Voltage Setting Q
Inverter
Voltage
E1-01
Setting
Overvoltage Trip Braking Transistor Stall
Level
Trip Reset ON OFF
230 150 - 255 400V 380V 380V 375V 380V
460 >400 800V 760V 760V 750V 760V
460 <400 720V 680V 660V 650V 670V
E1-02 Motor Capacity Selection Q
E1-03 Motor Rated Voltage Q
Section E: Motor Parameters
E1 V/f Pattern