Appendix G MSG-SND/MSG-RCV Functions (Ethernet)
G.1 Message Transmit Function (MSG-SND)
A-78
( 2 ) Process Result (PARAM00)
The process result is output to the upper byte. The lower byte is used for system analysis.
When an error occurs, take corrective action by referring to the following error contents:
Value of Process
Result
Meaning
00H In process (Busy)
10H Process completed (Complete)
8yH Error occurred (Error)
Value of Process
Result
Error Contents Description
80H
Reserved
81H
––
82H Error in setting address
The following setting is out of range. Check the setting.
PARAM05 (data address)
PARAM11 (register offset)
83H Data size error
The transmit or receive data amount is out of range.
Check PARAM06 (data size).
84H Error in setting circuit number
The circuit number is out of range.
Check Cir-No (circuit number) of the MSG-SND function.
85H Error in setting channel number
The communication buffer channel number is out of range.
Check Ch-No (communication buffer channel number) of the MSG-
SND function.
86H Connection number error
The connection number is out of range.
Check PARAM02 (connection number).
87H
Reserved
88H Communication section error
An error response was returned from the communication section (com-
munication device). Check the equipment connection. In addition, con-
firm that the remote device is open to communication.
89H Device select error
Unavailable device is set. Check Dev-Typ (communication device
type) of the MSG-SND function.