6.4 Communication with PLC Manufactured by Mitsubishi Electric Corporation (MELSEC protocol)
6.4.1 When the MP2300S Acts as Slave (automatic receive function is used)
6-78
3. Click the Easy Setting Button in the Message Communication area of the connection parameter set-
ting.
4. Set up the communication settings in the Message Communication Easy Setting Window.
How to set up in the Message Communication Easy Setting Window
c When automatic receive is used, select “1” for the Connect No.
d Set Port No. of MP2300S side (“10001,” for example).
e Select MELSEC for Communication Protocol Type, and click the Default Button.
f Select Connect Type (TCP, for example).
g Select Code (BIN, for example).
h Set Node port IP Address for the other device (MELSEC Q series) to be connected (“192.168.001.002,” for
example).
i Set Port No. of the other device (MELSEC Q series) to be connected (“10001,” for example).
j Click OK.