6.2 Communication with Other MP Series
6.2.2 When the MP2300S Acts as Slave (ladder program which uses a MSG-RCV function)
6-20
3. Click the Easy Setting Button in the Message Communication area of the connection parameter set-
ting.
4. Set a communication setting in the Message Communication Easy Setting Window.
How to set up in the Message Communication Easy Setting Window
c When automatic receive is used, select “2” for the Connect No.
d Set Port No. of the MP2300S side (“10002,” for example).
e Select Extended MEMOBUS for Communication Protocol Type, and click the Default Button.
f Select Connect Type (TCP, for example).
g Select Code (BIN, for example).
h Set Node Port IP Address for the other device (MP2300) to be connected (to “192.168.001.002,” for exam-
ple).
i Set Port No. of the other device (MP2300) to be connected (to “10002,” for example).
j Click OK.
c
d e f
h
g
i
j