3 Commands for Preparation Process
3.2.5 Check Device ID (ID_RD: 03H)
3-10
3.2.5 Check Device ID (ID_RD: 03H)
Send ID_RD command to read the device ID for confirmation.
(1) ID_RD Command (03H)
The specifications of the ID_RD command are described below.
Byte ID_RD
Description
Command Response
1 03H 03H
Phases in
which the
command can
be executed
Phase 2 and 3
Synchronization
classification
Asynchronous
command
2ALARM
Processing
time
Within commu-
nications cycle
Subcommand Can be used
3
STATUS
Reads the device ID for contirmation.
Use DEVICE_CODE to specify the device ID to be read.
Use OFFSET to specify which data of the device ID is to be read out.
Use SIZE to specify the number of data (bytes) to be read out.
A warning will occur and the command will be ignored in the following
case.
- DEVICE_CODE is set out of the range: Data setting warning 2
(A.94B)
4
5
DEVICE_
CODE
DEVICE_
CODE
6 OFFSET OFFSET
7SIZE SIZE
8
ID
9
10
11
12
13
14
15
16 WDT RWDT
17
Subcommand