48 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
If b1-01 = “1: Terminals” then the analog input A1 will be used instead of Setpoint Reference 1 for the first preset Setpoint. If b1-01 =
“0: Operator,” then Setpoint Reference 1 will be used.
If H3-09 = “2: Aux Reference” then the analog input A2 will be used instead of Setpoint Reference 2 for the second preset Setpoint. If
H3-09 = 2 then Setpoint Reference 2 will be used. This is only available when the iQpump drive is operating in the speed mode.
Important: The programming of d1-01 through d1-04 and d1-17 will be affected by the setting of P1-02 and o1-03, respectively. The
programming of these parameters will be in the units specified by Display Scaling parameter (P1-02 and o1-03).
Note: This function is only used with the LCD operation, not used with HOA operator.