YASKAWA TM.iQp.07 iQpump Controller Programming Manual 213
Figure 1.164
Figure 168. Low Flow Fault Auto Restart (P6-07 = 3)
Figure 1.165
Figure 169. Sleep Level Type = Flow Meter (P2-01 = 4)
Table 88 Parameters <0034>
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
P2-01 060A
Sleep Level Type
Sleep Lvl Type
Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
3: Output Speed (rpm)
<0034>
4: Low Flow (Terminal A1 - Flow meter required) <0034>
Note: Feedback depends on PID direction operation.
Displays a “Sleep” Alarm when active.
0 ~ 4 0 Programming
Run
command
Restart
counter
Flow Rate
Term A1)
Output
Frequency
Low Flow
LOWFL
Fault
1
P6-05
P6-06
P6-08
P6-04
P6-05
P6-06
P6-05
Run Cmd.
Output
Frequency
P6-06
Low Flow Time St
PI
Feedback
PI Setpoint
Start Level (P1-04)
Sleep
Active
Sleep Level
Flow Meter
(Term A 1)
P2-03
Sleep Delay Time
P1-05
S-Lvl Delay Time
P6-06
Low Flow Time St
P2-02
Vista de pagina 212