YASKAWA TM.iQp.07 iQpump Controller Programming Manual 169
Figure 1.120
Figure 124.
Figure 1.121
Figure 125.
Figure 1.122
Figure 126.
The sleep function can be active during the following conditions:
When P2-20 is set to 0 or 3
<0034> (disabled), the output frequency must be greater than the Sleep Level (P2-02).
When P2-20 is greater than P2-02, the output frequency must be greater than Alternative Sleep Activation Level (P2-20). See
Figure 124..
When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20). See Figure 125..
When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20) and Sleep Level (P2-02). See Figure 126.
A value of 0 programmed in P2-20 will disable this function.
P2-01 = 0: Display based on “Hz”
<0034>
P1-06
SLEEP MODE
SLEEP PERMITTED
P2-02
P2-20
P2-03
P1-06
SLEEP PERMITTED
P2-02
P2-20
P2-03
SLEEP MODE
P1-06
SLEEP MODE
SLEEP PERMITTED
P2-02
P2-20
P2-03