1
.
VS-606PC3
INVERTER
MAIN
UNIT
(Confd)
1
.7 .2
High
Voltage
Test
Use
an
insulation
resistance
tester
(500
V)
to
conduct
,
insulation resistance
test
(high
voltage
test)
on
the
main
LUZ
control
circuit as
described
below
.
(1)
Remove
the
inverter
main
circuit
and
control
circuit
terminal
wiring
and
execute
the
test
only
between
the
main
circuit
terminals
and ground
(ground
terminal
G)
as
shown
in
Fig
.
1
.9
.
(2)
The
equipment
is
normal
with
the
insulation
resistance
tester
indicating
1
M
fl
or
more
.
VS-606P
11
-
13
L
1
L2 L3
T
1
T2T3
W'B2
Note
:
Do
not
conduct
high
voltage
test
on
the
control
circuit
terminals
.
Fig
. 1
.9
High
Voltage
Test
Vista de pagina 55