t
.
VS-606PC
3
INVERTER
MAIN
UNIT
(Cont
-
d)
(b)
Grounding
Ground
the
casing
of
the
VS-606PC3
using
ground
terminal
G
.
(1)
Ground
resistance
should
be
100
SZ
or
less
.
(2)
Never
ground
VS-606PC3
in
common
with
welding
machines,
motors,
or
other
large-
current
electrical
equipment,
or
a
ground
pole
.
Run
the
ground
lead
in
a
conduit
separate
from
leads
for
large-current
electrical
equipment
.
(3)
Use
the
ground
leads
which
comply
with
AWG
standards
and
make
the
length
as
short
as
possible
.
(4)
Where
several
VS-606PC3
units
are
used
side
by
side,
all
the units
should
be
grounded
as
shown
in
(a)
or
(b)
of Fig
1
.4
.
Do
not
form
a
loop
with
the
ground
leads
as
shown
in
(c)
.
QW
1
LM4
(a)
GOOD
(b)
GOOD
(c)
POOR
Fig
.
1
.4
Grounding
of
Three
VS-6()6PC3
Units