Installation 1-9
# Run/Stop and Frequency Reference Command Source Selection
The run/stop and frequency reference commands can originate from serial communication, the operator keypad, external terminals, or the
PROFIBUS-DP Option. Parameter b1-02 (Operation Method Selection) allows the selection of the origin of the run/stop commands.
Parameter b1-01 (Reference Selection) allows the selection of the origin of the frequency reference. The run/stop and frequency reference
commands may have different origins. For example, the run/stop command may be set to External Terminals (b1-02 = 1) while the
Frequency Reference may be set to Option PCB (PROFIBUS-DP Option) (b1-01 = 3).
Table 1.5 – – Frequency Reference Source Selection
b1-01 Frequency Reference Selection
0 Operator keypad
1 External Terminals
2 Serial Communication
3 Option PCB (PROFIBUS-DP Option)
4 Pulse input (Available on F7 and G7 drives only)
Table 1.6 Operation Method Selection
b1-02 Operation Method Selection (Run/Stop)
0 Operator keypad
1 External Terminals
2 Serial Communication
3 Option PCB (PROFIBUS-DP Option)