5.10 System Function Instructions
5.10.6 Send Message (MSG-SND)
5-243
Instructions
5
[ a ] Parameter Details
This section describes the parameters in detail. The parameter number corresponds to the word offset from the first
address of the parameter list.
For example, if the first address of the parameter list is MA00100, set the value in MW00110 to set PARAM10.
Processing Result (PARAM00)
This parameter outputs the result of processing to the upper byte. The lower byte is used for system analysis.
• 00 hex: Processing (Busy)
• 10 hex: Processing completed (Complete)
• 8 hex: Error
The following errors can occur.
•81 hex: Function code error
An attempt was made to send an unused function code. Or an unused function code was received.
•82 hex: Address setting error
The data address, coil offset, input relay offset, input register offset, or hold register offset is out-
side of the valid range.
•83 hex: Data size error
The size of the send or receive data was set outside of the valid range.
•84 hex: Circuit number setting error
The set circuit number is outside of the valid range.
•85 hex: Channel number setting error
The set channel number is outside of the valid range.
•86 hex: Station address error
The set station number is outside of the valid range.
•88 hex: Communications section error
The communications section returned an error response.
•89 hex: Device selection error
A device that cannot be used was selected.
Parameter No. IN/OUT
Description
MEMOBUS No-protocol
PARAM00 OUT
Processing result Processing result
PARAM01 OUT
Status Status
PARAM02 IN
Remote station number Remote station number
PARAM03 SYS
Reserved for system. Reserved for system.
PARAM04 IN
Function code
PARAM05 IN
Data address Data address
PARAM06 IN
Data size Data size
PARAM07 IN
Remote CPU number Remote CPU number
PARAM08 IN
Coil offset
PARAM09 IN
Input relay offset
PARAM10 IN
Input register offset
PARAM11 IN
Hold register offset Register offset
PARAM12 SYS
Reserved for system. Reserved for system.
PARAM13 SYS
Reserved for system. Reserved for system.
PARAM14 SYS
Reserved for system. Reserved for system.
PARAM15 SYS
Reserved for system. Reserved for system.
PARAM16 SYS
Reserved for system. Reserved for system.