Yaskawa MP900 Series Ladder Programming Manual Manual de usuario Pagina 189

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 415
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 188
5.7 Data Shift Instructions
5.7.5 Exchange (XCHG)
5-120
5.7.5 Exchange (XCHG)
( 1 ) Operation
The XCHG instruction exchanges the designated number of words to move between table 1 and table 2.
The data contents of table 1 and table 2 specified by data table start 1, data table start 2, and the number of words to
move are exchanged.
( 2 ) Format
C and # registers cannot be used.
Table 1 data
table start 1
Table 2 data
table start 2
Number of words
to move
1
2
3
4
5
11
12
13
14
15
Table 1 Table 2
11
12
13
14
15
1
2
3
4
5
Data exchanged.
6 16 6 16
Data table start 2
Number of words
to move
Data table start 1
Icon:
Key entry: XCHG
Parameter Name
Applicable Data Types
B W L F A Index Constant
Data table start 1
(Table1)
×
{
*
×××××
Data table start 2
(Table2)
×
{
×××××
Number of words to move
(Width)
×
{
×××
{{
Vista de pagina 188
1 2 ... 184 185 186 187 188 189 190 191 192 193 194 ... 414 415

Comentarios a estos manuales