9.9 Inverter Constant Write Function (ICNS-WR)
9-31
9.9 Inverter Constant Write Function (ICNS-WR)
[Outline]
Writes the inverter constants.
The types and ranges of the inverter constants to be written can be designated.
[Applicable inverters] connected via MP930, SVB-01, CP-215
[Format]
Symbol : ICNS-WR
Full Name : Inverter-Constant Write
Category : SYSTEM
Icon :
[Parameter]
I/O
Definition
Parameter Name
I/O
Designation
Setting
Execute B-VAL Inverter constant write command
Abort B-VAL Inverter constant write forced interruption command
Type of transmission device
Dev-Typ I-REG
215IF = 1 MP930 = 4 SVB-01 = 11
Line No.
Cir-No I-REG
215IF = 1, 2 MP930 = 1 SVB-01 = 1 to 16
Slave station No.
St-No I-REG
215IF = 1 to 64 MP930 = 1 to 14 SVB-01 = 1 to 14
Transmission buffer channel No.
Ch-No I-REG
215IF = 1 to 3 MP930 = 1 SVB-01 = 1 to 8
Cns-Typ I-REG Type of inverter constant
0 = direct designation of reference No. 1 = An, 2 = Bn, 3 = Cn,
4 = Dn, 5 = En, 6 = Fn, 7 = Hn, 8 = Ln, 9 = On, 10 = Tn
Cns-No I-REG Inverter constant No. (1 to 99)
The upper limit will differ according to the type of inverter.
If Cns-Typ = 0,designate the reference No.
Cns-Size
I-REG Number of inverter constants (number of data to be written)1 to
100
Input
Dat-Adr Address input Register address of set data (address of MW, DW, or #W)
Busy B-VAL Inverter constants are being written in.
Complete B-VAL The write-in of inverter constants has been completed.
Error B-VAL Occurrence of error
Output
Status I-REG Inverter constant write execution status