Option Error Codes
n
Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive
digital operator as shown in Table 9.
Table 9 Option Fault Monitor Descriptions
Fault
Condition
Fault Declared
Status Value
(U6-98/U6-99)
Description
No Fault n/a 0 No faults
Force Fault EF0 3
Network sent a message to force this node
to the fault state.
Connection
Timeout
BUS ERROR 1101 The control connection timed out.
Duplicate IP
Address
BUS ERROR 1102
This node and at least one other node have
the same IP Address.
Default MAC
Address
None 1103
Factory default MAC Address
programmed into the option. Return for
reprogramming.
Network Link
Down
BUS ERROR 1104 No network link to option.
Hardware Error BUS ERROR 1105
Option card hardware has stopped
functioning. Cycle power to the drive.
Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared
upon drive power-up.
U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset
and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the
original fault value and U6-99 stores the new fault status value.