7 Modbus TCP/IP Messaging
36 YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual
Table 8 Drive Registers
Address
(hex)
Drive
Register
(hex)
Description Bit Description
2000 4B
Status Word
(U1-12)
0 During Run
1 During Zero Speed
2 During Reverse Direction
3 During Fault Reset Signal Input
4 During Speed Agree
5 Drive Ready
6Alarm
7Fault
8 During Operation Error (oPE)
9 During Momentary Power Loss
A Motor 2 Selected
B Reserved
C Reserved
D Reserved
E ComRef Status, NetRef Status
F ComCtrl Status, NetCtrl Status
2001 44 Motor Speed Monitor (U1-05)
2002 48 Torque Reference Monitor (U1-09)
2003 F0 PG Count Channel 1
2004 40 Frequency Reference Monitor (U1-01)
2005 41 Output Frequency Monitor (U1-02)
2006 26
Output Current
(0.01 A units for drives set to 11 kW in Heavy or Normal Duty and 0.1 A units for drives
set to 15 kW and above.)
2007 4F Terminal A2 Input Level Monitor (U1-14)
2008 46 DC Bus Voltage Monitor (U1-07)
Modbus_IM_E_conditional.fm 36 ページ 2012年10月31日 水曜日 午後1時45分